B
Very limited contribution to fire
The material does not spread fire quickly in the SBI test. This is the same for B-s3,d0 and B-s1,d0.
OEM / FIRE CLASS GUIDE · EN 13501-1
B-s3,d0 is the fire class many European FEF datasheets carry. B-s1,d0 is the stricter smoke class. Both are B on fire contribution; the difference is smoke — and, in practice, formulation and test scope. This guide explains the difference, when each is specified, and how to write it into an OEM specification.
THE ONE-MINUTE ANSWER
EN 13501-1 writes the class as three parts: fire contribution, smoke and flaming droplets. Read the suffix, not just the letter.
| Class | Fire contribution | Smoke | Flaming droplets | Typical position |
|---|---|---|---|---|
| C-s3,d0 | Limited | High | None | Lower-cost offer |
| B-s3,d0 | Very limited | High | None | Common European FEF |
| B-s1,d0 | Very limited | Low | None | Low-smoke / high-safety specification |
C-s3,d0 is included only to show the ladder; it is not the subject of this guide. A higher letter is better on fire contribution; a lower smoke number is better on smoke.
B
The material does not spread fire quickly in the SBI test. This is the same for B-s3,d0 and B-s1,d0.
s1
s1 is the low-smoke level. s3 allows more smoke. This is the main difference between B-s1,d0 and B-s3,d0.
d0
No flaming droplets or particles within the test period. This is the same for B-s3,d0 and B-s1,d0.
The suffix is not decoration. B-s1,d0 and B-s3,d0 are different classifications, not synonyms.
The letter B is only part of the job. Smoke performance is where formulations and test scope separate suppliers.
Smoke is driven by the flame-retardant system, fillers and cell structure. A formulation that reaches B-s3,d0 may not reach s1.
EN 13501-1 classification is tied to the tested construction: thickness, density, facing and product form. A change can require a new test.
EN ISO 11925-2 (small flame) and EN 13823 (SBI) feed the classification. You cannot infer one class from a datasheet alone.
This is why a supplier’s B-s1,d0 sheet does not automatically cover a tube, a different thickness or a different facing.
Start from the building’s fire strategy, then write the class into the specification. The table is a buying guide, not a fire-engineering conclusion.
| Project / specification | Usually specified | What to check |
|---|---|---|
| Standard HVAC, chilled water, cold rooms | B-s3,d0 | Local fire strategy; thickness and facing |
| Hospitals, cleanrooms, low-smoke specifications | B-s1,d0 | Smoke requirement; test scope |
| Data centres, public buildings | B-s1,d0 | Fire engineer’s specification |
| Transport and high-risk areas | B-s1,d0 or project-specific | Project-specific test and approval |
The final requirement comes from the building’s fire strategy and the authority having jurisdiction. Use this table to ask better questions, not to replace the fire engineer.
A class without a product scope is not a specification. Send the scope with the class.
Send this to each supplier and ask for the exact product scope behind the class. If the answer is a datasheet line without thickness, facing and report number, keep asking.
Reaction to fire and product performance are separate questions. A fire class does not answer the product-standard question.
EN 13501-1
Answers: how does the product behave in a fire? Produces the Euroclass — for example B-s3,d0 or B-s1,d0.
EN 14304
Answers: dimensions, thermal conductivity, water vapour diffusion, mechanical properties and durability.
CE / DoP
Follows the applicable harmonised standard and the EU economic operator’s obligations. Not the same as a fire class.
A B-s1,d0 classification alone does not make a product EN 14304-compliant or CE-marked.
In an OEM relationship, the brand owner and the production site are different roles. Write the roles down before the first shipment.
| Role | Responsibility | Typical holder |
|---|---|---|
| Brand owner | Brand, specification, market | Customer |
| EU economic operator / importer | DoP, CE marking, importer obligations | Customer |
| Production site | Factory production control, batch records, test samples | Partner plant |
| Notified body | Classification / test report | Independent lab |
| VXEL | Supply-chain coordination, QC, documentation, audit access | VXEL |
Roles are contractual. Confirm them with your notified body and legal advisor before you place the brand on the EU market.
We can organize EN 13501-1 B-s1,d0 and B-s3,d0 programs at our partner site. Your SKU is produced to your specification; testing and report ownership are agreed in the OEM contract. We do not transfer someone else’s report.
B-s3,d0 availability depends on thickness, facing and volume Feasibility is confirmed before quotation
OEM & private label overview → VXEL own-brand EN 13501-1 / EN 14304 track →Production is carried out at partner plants. VXEL organizes the program and sets the quality standard.
Certificate and DoP roles are agreed in the OEM contract. We do not present someone else's report as a VXEL certificate.
A GB 8624 B1 result is not an EN 13501-1 classification. We do not translate one into the other.
It is a reaction-to-fire classification. EN 14304, a DoP and CE marking are a separate route.
We do not claim B-s1,d0 for a construction that has not been tested for the program.
We do not name our production partner on this website. Factory identity and audit access are shared at the NDA / audit stage.
Both are EN 13501-1 B classifications: very limited contribution to fire, with no flaming droplets (d0). B-s1,d0 adds low smoke production (s1); B-s3,d0 allows higher smoke (s3). The difference is smoke, and in practice the formulation and test scope behind it.
On smoke performance, B-s1,d0 is the stricter class. Whether it is required depends on the building’s fire strategy. B-s3,d0 is common for standard HVAC and cold-room work; B-s1,d0 is specified where low smoke matters.
Use B-s3,d0 for standard HVAC, chilled water and cold-room work where the fire strategy accepts higher smoke. Specify B-s1,d0 for hospitals, data centres, public buildings and low-smoke specifications. Confirm the final requirement with your fire engineer.
No. B-s1,d0 is a reaction-to-fire classification under EN 13501-1. CE marking and a Declaration of Performance follow the EN 14304 route and are separate from the fire classification.
No. A classification is product-specific and tied to a defined construction. Your SKU must be tested for your program; report ownership and scope are agreed in the OEM contract.
Yes. EN 13501-1 classifications are tied to the tested construction, including thickness, density and facing. A change can require a new test or an extension of the existing report.
We can review B-s3,d0 and B-s1,d0 specifications. Feasibility depends on thickness, facing and volume, and is confirmed before quotation. We do not claim a class for an untested SKU.
Yes. We can sign a mutual NDA and non-circumvention agreement before receiving specifications or factory data.
Product, thickness, facing, volume and target market. If you need an NDA first, say so — we will send one before asking for specifications.