OEM / FIRE CLASS GUIDE · EN 13501-1

B-s3,d0 or B-s1,d0?
What European OEM buyers need to know

B-s3,d0 is the fire class many European FEF datasheets carry. B-s1,d0 is the stricter smoke class. Both are B on fire contribution; the difference is smoke — and, in practice, formulation and test scope. This guide explains the difference, when each is specified, and how to write it into an OEM specification.

8 MIN READ · FOR SPECIFIERS, BUYERS AND BRAND OWNERS

THE ONE-MINUTE ANSWER

Standard HVAC, cold rooms, general pipework B-s3,d0 is usually sufficient — confirm with your fire engineer.
Hospitals, data centres, public buildings, low-smoke specs B-s1,d0 is the class to specify.
Neither class is a CE mark B-s1,d0 is a reaction-to-fire classification; CE marking and a DoP are a separate route.
01 / THE TABLE

The difference in one table

EN 13501-1 writes the class as three parts: fire contribution, smoke and flaming droplets. Read the suffix, not just the letter.

TABLE FC-01 · EN 13501-1 CLASSES FOR FEF B-s3,d0 / B-s1,d0
Class Fire contribution Smoke Flaming droplets Typical position
C-s3,d0 Limited High None Lower-cost offer
B-s3,d0 Very limited High None Common European FEF
B-s1,d0 Very limited Low None Low-smoke / high-safety specification

C-s3,d0 is included only to show the ladder; it is not the subject of this guide. A higher letter is better on fire contribution; a lower smoke number is better on smoke.

02 / THE CODE

What each part of B-s1,d0 means

B

Very limited contribution to fire

The material does not spread fire quickly in the SBI test. This is the same for B-s3,d0 and B-s1,d0.

s1

Low smoke production

s1 is the low-smoke level. s3 allows more smoke. This is the main difference between B-s1,d0 and B-s3,d0.

d0

No flaming droplets

No flaming droplets or particles within the test period. This is the same for B-s3,d0 and B-s1,d0.

The suffix is not decoration. B-s1,d0 and B-s3,d0 are different classifications, not synonyms.

03 / WHY IT IS HARDER

Why B-s1,d0 is harder than B-s3,d0

The letter B is only part of the job. Smoke performance is where formulations and test scope separate suppliers.

  • 01

    Formulation-sensitive

    Smoke is driven by the flame-retardant system, fillers and cell structure. A formulation that reaches B-s3,d0 may not reach s1.

  • 02

    Test scope is product-specific

    EN 13501-1 classification is tied to the tested construction: thickness, density, facing and product form. A change can require a new test.

  • 03

    Two test methods, one classification

    EN ISO 11925-2 (small flame) and EN 13823 (SBI) feed the classification. You cannot infer one class from a datasheet alone.

This is why a supplier’s B-s1,d0 sheet does not automatically cover a tube, a different thickness or a different facing.

04 / THE DECISION

Which class do you need?

Start from the building’s fire strategy, then write the class into the specification. The table is a buying guide, not a fire-engineering conclusion.

TABLE FC-02 · SPECIFICATION DECISION CONFIRM WITH FIRE ENGINEER
Project / specification Usually specified What to check
Standard HVAC, chilled water, cold rooms B-s3,d0 Local fire strategy; thickness and facing
Hospitals, cleanrooms, low-smoke specifications B-s1,d0 Smoke requirement; test scope
Data centres, public buildings B-s1,d0 Fire engineer’s specification
Transport and high-risk areas B-s1,d0 or project-specific Project-specific test and approval

The final requirement comes from the building’s fire strategy and the authority having jurisdiction. Use this table to ask better questions, not to replace the fire engineer.

05 / THE SPECIFICATION

How to specify it

A class without a product scope is not a specification. Send the scope with the class.

Reaction to fire: EN 13501-1 B-s1,d0 (or B-s3,d0) Product: flexible elastomeric foam — sheet / tube Thickness: ___ mm Density: ___ kg/m³ Facing: ___ Service temperature: ___ °C Documentation: classification report, batch traceability, DoP/CE as applicable

Send this to each supplier and ask for the exact product scope behind the class. If the answer is a datasheet line without thickness, facing and report number, keep asking.

06 / TWO DIFFERENT STANDARDS

EN 13501-1 is not EN 14304

Reaction to fire and product performance are separate questions. A fire class does not answer the product-standard question.

EN 13501-1

Reaction to fire

Answers: how does the product behave in a fire? Produces the Euroclass — for example B-s3,d0 or B-s1,d0.

EN 14304

Harmonised product standard

Answers: dimensions, thermal conductivity, water vapour diffusion, mechanical properties and durability.

CE / DoP

Market route

Follows the applicable harmonised standard and the EU economic operator’s obligations. Not the same as a fire class.

A B-s1,d0 classification alone does not make a product EN 14304-compliant or CE-marked.

07 / CE MARKING AND DoP

Who holds what in a private-label program

In an OEM relationship, the brand owner and the production site are different roles. Write the roles down before the first shipment.

Role Responsibility Typical holder
Brand ownerBrand, specification, marketCustomer
EU economic operator / importerDoP, CE marking, importer obligationsCustomer
Production siteFactory production control, batch records, test samplesPartner plant
Notified bodyClassification / test reportIndependent lab
VXELSupply-chain coordination, QC, documentation, audit accessVXEL

Roles are contractual. Confirm them with your notified body and legal advisor before you place the brand on the EU market.

08 / WHAT VXEL CAN SUPPLY

B-s1,d0 capability, without borrowing a certificate

We can organize EN 13501-1 B-s1,d0 and B-s3,d0 programs at our partner site. Your SKU is produced to your specification; testing and report ownership are agreed in the OEM contract. We do not transfer someone else’s report.

CLASSB-s1,d0
SCOPEsheet and tube
STANDARDEN 13501-1
EVIDENCEReport details and factory access at NDA / audit
NEW SKUTesting and report ownership per contract

B-s3,d0 availability depends on thickness, facing and volume Feasibility is confirmed before quotation

OEM & private label overview → VXEL own-brand EN 13501-1 / EN 14304 track →
09 / WHAT WE DO NOT CLAIM

Six things you will not see from us

  • 01

    We do not own a factory

    Production is carried out at partner plants. VXEL organizes the program and sets the quality standard.

  • 02

    VXEL is not the certificate holder

    Certificate and DoP roles are agreed in the OEM contract. We do not present someone else's report as a VXEL certificate.

  • 03

    A GB B1 result is not a Euroclass

    A GB 8624 B1 result is not an EN 13501-1 classification. We do not translate one into the other.

  • 04

    B-s1,d0 is not CE marking

    It is a reaction-to-fire classification. EN 14304, a DoP and CE marking are a separate route.

  • 05

    No class for an untested SKU

    We do not claim B-s1,d0 for a construction that has not been tested for the program.

  • 06

    No public factory name

    We do not name our production partner on this website. Factory identity and audit access are shared at the NDA / audit stage.

10 / FAQ

Questions buyers ask

What is the difference between B-s3,d0 and B-s1,d0?

Both are EN 13501-1 B classifications: very limited contribution to fire, with no flaming droplets (d0). B-s1,d0 adds low smoke production (s1); B-s3,d0 allows higher smoke (s3). The difference is smoke, and in practice the formulation and test scope behind it.

Is B-s1,d0 better than B-s3,d0?

On smoke performance, B-s1,d0 is the stricter class. Whether it is required depends on the building’s fire strategy. B-s3,d0 is common for standard HVAC and cold-room work; B-s1,d0 is specified where low smoke matters.

Which FEF fire class should I specify?

Use B-s3,d0 for standard HVAC, chilled water and cold-room work where the fire strategy accepts higher smoke. Specify B-s1,d0 for hospitals, data centres, public buildings and low-smoke specifications. Confirm the final requirement with your fire engineer.

Does B-s1,d0 mean the product is CE marked?

No. B-s1,d0 is a reaction-to-fire classification under EN 13501-1. CE marking and a Declaration of Performance follow the EN 14304 route and are separate from the fire classification.

Can I use your B-s1,d0 report for my product?

No. A classification is product-specific and tied to a defined construction. Your SKU must be tested for your program; report ownership and scope are agreed in the OEM contract.

Does thickness or facing affect the classification?

Yes. EN 13501-1 classifications are tied to the tested construction, including thickness, density and facing. A change can require a new test or an extension of the existing report.

Can you produce B-s3,d0 as well?

We can review B-s3,d0 and B-s1,d0 specifications. Feasibility depends on thickness, facing and volume, and is confirmed before quotation. We do not claim a class for an untested SKU.