PRODUCTS / 02 · TUBE
FEF insulation tube · ID 6 – 168 mm
Pre-formed closed-cell tubes that slip onto the pipe and close in one pass. Wall 6 – 50 mm, standard length 2 m, three ID bands. Thermal conductivity 0.034 W/(m·K), fire performance GB 8624 B1, service temperature -50~110℃, produced to GB/T 17794.
Also available: sheets · matching adhesive · all products
Standard sizes
| Inside diameter | Wall thickness | Length |
|---|---|---|
| 6 – 35 mm | 6 / 9 / 13 / 19 / 25 mm | 2 m |
| 42 – 89 mm | 9 / 13 / 19 / 25 / 32 mm | 2 m |
| 108 – 168 mm | 19 / 25 / 32 / 40 / 50 mm | 2 m |
Final specification follows the quotation and the batch. Bespoke diameters — we welcome custom work that many suppliers will not take on; if a mould does not exist, we say so up front.
Nominal values, tested batch by batch
Items marked Pending confirmation are in the 12-item test programme; no figure is published before its report is issued.
| Property | Value | Standard |
|---|---|---|
| Thermal conductivity λ | ≤ 0.034 W/(m·K) | GB/T 17794 |
| Fire performance | B1 (difficult to ignite) | GB 8624 |
| Service temperature | -50 ~ 110℃ | — |
| Water-vapour resistance factor μ | Pending confirmation | GB/T 17794 |
| Oxygen index | Pending confirmation | GB/T 17794 |
| Density | Pending confirmation | GB/T 17794 |
Batch-tested to the published QC-01 standard; batch reports ship with the goods and trace to the production date. European standards EN 14304 / EN 13501-1: not yet submitted, no claim.
Which wall, which band
Quick rules of thumb for tube work; confirm with the thickness calculator and send it to us for a free check.
- Cooling / chilled water
- Size by dew-point margin for anti-condensation, typically 19 – 25 mm wall, thicker in high humidity.
- Indoor plumbing
- 6 – 13 mm wall is usually enough; small footprint, fast to fit.
- Outdoor / high-humidity plant rooms
- Add 6 mm wall; low-temp stores: add 10 mm.
- Diameter add-on
- +6 mm wall at ≥54 mm, another +6 mm at ≥89 mm; round up to the 6/9/13/19/25/32/40/50 mm series.
- Regular specs
- Common ID bands and walls are kept available; custom runs are scheduled with lead time written into the contract.
Get the datasheet or a quotation
Send ID + wall + quantity + destination, e.g. “tube ID 28 × 19 mm × 600 m, Doha”. Reply within 24 hours.